Heat exchanger (part 2) - TheCNC2020 Blog

Heat exchanger (part 2)| TheCNC2020 You can find this article again with keywords: Heat transfer rate, Cost
Pumping power, Size and weight, Type, Materials, Other considerations

Heat exchangers are devices that facilitate the exchange of heat between two fluids that are at different temperatures while keeping them from mixing with each other.

Heat exchangers are commonly used in practice in a wide range of applications, from heating and air-conditioning systems in a household, to chemical processing and power production in large plants.


In the previous article, we knew the types of heat exchangers. So, what factors should you consider when choosing a heat exchanger? Let's find out together.

Heat exchangers are complex devices. To choose a heat exchanger is usually based on the heat transfer capacity. However, heat transfer enhancement in heat exchangers is usually accompanied by increased pressure drop, and thus higher pumping power. Therefore, any gain from the enhancement in heat transfer should be weighed against the cost of the accompanying pressure drop. Also, some thought should be given to which fluid should pass through the tube side and which through the shell side. Usually, the more viscous fluid is more suitable for the shell side (larger passage area and thus lower pressure drop) and the fluid with the higher pressure for the tube side.

Choosing the right heat exchanger depends on several factors:

Heat transfer rate

This is the most important quantity in the selection of a heat exchanger. A heat exchanger should be capable of transferring heat at the specified rate in order to achieve the desired temperature change of the fluid at the specified mass flow rate.

Cost

Budgetary limitations usually play an important role in the selection of heat exchangers, except for some specialized cases where “money is no object.” An off-the-shelf heat exchanger has a definite cost advantage over those made to order. However, in some cases, none of the existing heat exchangers will do, and it may be necessary to undertake the expensive and time-consuming task of designing and manufacturing a heat exchanger from scratch to suit the needs.

Therefore, the operating and maintenance costs of the heat exchanger are also important considerations in assessing the overall cost.

Pumping power

In a heat exchanger, both fluids are usually forced to flow by pumps or fans that consume electrical power. The annual cost of electricity associated with the operation of the pumps and fans can be determined from

Operating cost = (Pumping power, kW) x (Hours of operation, h) x (Price of electricity, $/kWh)

(where the pumping power is the total electrical power consumed by the motors of the pumps and fans)

Minimizing the pressure drop and the mass flow rate of the fluids will minimize the operating cost of the heat exchanger, but it will maximize the size of the heat exchanger and thus the initial cost. As a rule of thumb, doubling the mass flow rate will reduce the initial cost by half but will increase the pumping power requirements by a factor of roughly eight.

Typically, fluid velocities encountered in heat exchangers range between 0.7 and 7 m/s for liquids and between 3 and 30 m/s for gases. Low velocities are helpful in avoiding erosion, tube vibrations, and noise as well as pressure drop.

Size and weight

Normally, the smaller and the lighter the heat exchanger, the better it is. This is especially the case in the automotive and aerospace industries, where size and weight requirements are most stringent. A larger heat exchanger normally carries a higher price tag.

Type

The type of heat exchanger to be selected depends primarily on the type of fluids involved, the size and weight limitations, and the presence of any phase-change processes. A heat exchanger is suitable to cool a liquid by a gas if the surface area on the gas side is many times that on the liquid side. On the other hand, a plate or shell-and-tube heat exchanger is very suitable for cooling a liquid by another liquid.

Materials

The materials used in the construction of the heat exchanger may be an important consideration in the selection of heat exchangers. For example, the thermal and structural stress effects need not be considered at pressures below 15 atm or temperatures below 150°C. But these effects are major considerations above 70 atm or 550°C and seriously limit the acceptable materials of the heat exchanger.

A temperature difference of 50°C or more between the tubes and the shell will probably pose differential thermal expansion problems and needs to be considered. In the case of corrosive fluids, we may have to select expensive corrosion-resistant materials such as stainless steel or even titanium if we are not willing to replace low-cost heat exchangers frequently.

Other considerations

There are other considerations in the selection of heat exchangers that may or may not be important, depending on the application. For example, being leak-tight is an important consideration when toxic or expensive fluids are involved. Ease of servicing, low maintenance cost, and safety and reliability are some other important considerations in the selection process. Quietness is one

of the primary considerations in the selection of liquid-to-air heat exchangers used in heating and air-conditioning applications.